RKP-CMU1
Description :
RKP-CMU1 is a fully digitalized control / monitoring unit for the
RCP-2000 power system. Equipped with USB, RS-232, and ethernet
interface, it can be connected locally to PC to execute the control
and monitoring tasks. With built-in 4 configurable relay contacts,
users can flexibility monitor specific events or alarms and react
suitable action accordingly.
SELECTION GUIDE
Single unit: RKP-CMU1
Rack: RKP-1U I -CMU1
Features :
1U low profile/19-inch rack mounting
Control and monitor RCP-2000 units
Front panel LCD and buttons for on-site service without PC
USB-, RS-232 or Ethernet interface for PC connection locally or remote
monitoring and control via GSM modem
Alarm/event log with time and date
Windows-based PC communication software
Easy Wire Connections on Rear side
4 user programmable relay outputs for traditional remote monitoring
warning
3 years warranty
Whole System: RKP-6K1U I -CMU1- 12 Output voltage
I: AC Inlet (IEC320-C20)
T: Terminal block
I: AC Inlet (IEC320-C20)
T: Terminal block
SPECIFICATION
MODEL
RKP-1U -CMU1
RKP-CMU1
DIGITAL METER
Display the DC output voltage, current, and internal temperature of each RCP-2000 unit
OUTPUT CONTROL OUTPUT
LED INDICATOR
PM Bus signal for each RCP-2000 unit
Green: Power on Red:Alarm
RELAY CONTACT
4 user programmable relay, relay contact rating(max.): 30V/1A resistive
VOLTAGE RANGE Note.3 12 ~ 15VDC
INPUT CURRENT
1A/12VDC 0.8A/15VDC
MONITORING INPUTS
PM Bus signal for each RCP-2000 unit
DISPLAY
LCD 16x2 Alphanumeric Matrix Display / PC Web Page Display
MONITOR
FUNCTION CONTROL
Output Voltage / Load Current / Temperature / Input Voltage
Output Voltage Current Limit ON/OFF
COMM. INTERFACE
USB RS-232 Ethernet
WORKING TEMP.
Note.1 -25 ~ +70
ENVIRONMENT WORKING HUMIDITY
20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.7KVDC
SAFETY &
ISOLATION RESISTANCE Note.2 I/P-O/P, I/P-FG,O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
EMC EMC EMISSION
Compliance to EN55022 (CISPR22)
Design refer to TUV EN60950-1
-----
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2(EN5008-2), light industry level, criteria A
OTHERS
NOTE
DIMENSION
486.6*350.8*44mm (L*W*H)
PACKING
4.4Kg; 3pcs/14.2Kg/2.67CUFT
1. LCD may freeze under -10 .
2. RKP-CMU1 is a secondary side device, and only O/P-FG condition is considered.
3. Recommanded adaptor series: MEANWELL GS12, GS15, GS18, GE12, GE18.
147.5*127*41mm (L*W*H)
0.8Kg; 16pcs/13.8Kg/0.79CUFT
File Name:RKP-CMU1-SPEC 2011-11-10
Datasheet pdf - http://www.DataSheet4U.net/

1 page




RKP-CMU1 pdf
www.DataSheet.co.kr
1U Rack Control and Monitoring Unit
RKP-CMU1
CN500 IN/OUT Connector pins function description
Pin No.
1,7
2,8
3,9
4,10
5,11
6,12
13
14
15
16~21
22
23
24
25
Function Description
ON/OFF
Each unit can separately turn the output on and off by electrical signal or dry contact between ON/OFF A,B,C(pin 1,7,16) and
+5V-AUX(pin 13). Short: ON, Open:OFF. (Note.2)
AC-OK
DC-OK
PV
Low : When the input voltage is 87Vrms. High : when the input voltage in 75Vrms. (Note.2)
High : When the Vout 80 5%. Low : When Vout 80 5%. (Note.2)
Connection for output voltage trimming. The voltage can be trimmed within its defined range. (Note.1)
T-ALARM
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. (Note.2)
FAN FAIL High : When the internal fan fail. Low : When the internal fan is normal. (Note.2)
+5V-AUX
Auxiliary voltage output, 4.5 ~ 5.5V, referenced to GND-AUX (pin 15). The maximum load current is 0.3A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
+12V-AUX Auxiliary voltage output, 10.8 ~ 13.2V, referenced to GND-AUX (pin 15). The maximum load current is 0.8A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
GND-AUX Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
N.C. -----
+S Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
-S
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
+V Positive output voltage. For local sense use only, can't be connected directly to the load.
-V Negative output voltage. For local sense use only, can't be connected directly to the load.
JK1 IN/OUT Connector pins function description
Pin No. Function Description
1,2 DA,DB Differential digital signal for parallel control. (Note.1)
3 -V Negative output voltage. For parallel control, can't be connected directly to the load.
4 CONTROL Remote ON/OFF control pin used in the PMBus interface. (Note.2)
5 NC Not use.
6 SDA Serial Data used in the PMBus interface. (Note.2)
7 SCL Serial Clock used in the PMBus interface. (Note.2)
8 GND-AUX Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Note.1: Non-isolated signal, referenced to the output terminals (-V).
Note.2: Isolated signal, referenced to GND-AUX.
CN502 IN/OUT Connector pins function description
Pin No.
1,4,6,7,8,9
2
3
4
Function
NC
RXD
TXD
GND-FG
Description
Not used.
Receive data used in the RS-232 interface.
Transmit data used in the RS-232 interface.
RS-232 common GND. This signal connects to FG and isolated from V and GND-AUX.
CN503 IN/OUT Connector pins function description
Pin No.
1,3,5,7
2,4,6,8
Function
D-IN1
D-IN2
D-IN3
D-IN4
GND-FG
Description
The isolated digital input signal and referenced to GND-FG.
Open form GND-FG or +5V : Logic "0" input to RKP-CMU1
short to GND-FG or 0V : Logic "1" input to RKP-CMU1
Common GND for D-IN. This signal connects to FG and isolated from V and GND-AUX.
JK500 IN/OUT Connector pins function description
Pin No.
1,2
3,6
4,5,7,8
Function
TX+/TX-
RX+/RX-
NC
Description
Transmit data used in the Ethernet interface.
Receive data used in the Ethernet interface.
Not used.
File Name:RKP-CMU1-SPEC 2011-11-10
Datasheet pdf - http://www.DataSheet4U.net/

5 Page










PáginasTotal 7 Páginas
PDF Descargar[ Datasheet RKP-CMU1.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
RKP-CMU11U Rack Control and Monitoring UnitMean Well Enterprises
Mean Well Enterprises

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar