Datenblatt-pdf.com


E5GN Schematic ( PDF Datasheet ) - Omron

Teilenummer E5GN
Beschreibung Basic-type Digital Temperature Controller
Hersteller Omron
Logo Omron Logo 




Gesamt 17 Seiten
E5GN Datasheet, Funktion
Basic-type Digital Temperature Controller
E5GN (48 x 24 mm)
www.DataSheet4U.com
CSM_E5GN_DS_E_5_1
New 48 x 24-mm Basic Temperature
Controller with Enhanced Functions and
Performance. Improved Indication
Accuracy and Preventive Maintenance
Function.
• Indication Accuracy
Thermocouple input: ±0.3% of PV (previous models: ±0.5%)
Pt input: ±0.2% of PV (previous models: ±0.5%)
Analog input: ±0.2% FS (previous models: ±0.5%)
E5GN
Models with Screw Terminal
Blocks
48 × 24 mm
E5GN--@-C
Models with Screwless Clamp
Terminal Blocks
48 × 24 mm
• Models are available with screw terminal blocks or screwless
clamp terminal blocks.
• A PV/SV-status display function can be set to automatically
alternate between displaying the status of the Temperature
Refer to Safety Precautions for E5@N/E5@N-H.
Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV.
• Preventive maintenance for relays in the Temperature Controller
Refer to Operation for E5@N/E5@N-H for operating
procedures.
using a Control Output ON/OFF Counter.
• Switch the PV display between three colors.
• Compatible with Support Software (CX-Thermo version 4.2 or higher).
• Eleven-segment displays.
• Models are available with one or two alarm outputs.
Main I/O Functions
Event Inputs
None
• Two
Sensor Inputs
• Universal thermocouple/Pt inputs
(Models with temperature inputs)
• Analog current/voltage inputs
(Models with analog inputs)
Indication Accuracy
• Thermocouple input: ±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% FS
Sampling Period
• 250 ms
E5GN
Dual Display: PV and SV
4-digit Display
Auxiliary Outputs
None
• One
• Two
Control Output 1
• Relay output
Voltage output (for driving SSR)
• Current output
• Auto/manual switching
• Temperature Controller status display
• Simple program function
• Control output ON/OFF count alarm
• PV change rate alarm
• Models also available with RS-232C
communications
• Models also available with RS-485
communications
This datasheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)
1






E5GN Datasheet, Funktion
E5GN
www.DataSheet4U.com
Controllers with Screwless Clamp Terminal Blocks
Models with Temperature Inputs
Models with One Control Output and a 100 to 240-VAC Power Supply
Case color
Control
output
Control
mode *1
No. of
auxiliary
outputs
Detection
of heater
burnout,
SSR failure,
and heater
overcurrent
No. of event
inputs
Transfer
output *2
Standard ---
---
2
1 ---
Relay output Standard or
heating/
cooling
2
Black
Standard ---
1
Voltage
output (for Standard or
driving SSR) heating/
cooling
2
Current
output
Standard or
heating/
1
cooling
---
Detection for
single-
phase
heaters
---
2
---
---
2
---
---
Detection for
single-
phase
heaters
---
2
---
---
2
---
---
---
Transfer
output using
control
output
Communic
ations
---
RS-232C
RS-485
---
RS-485
---
RS-232C
RS-485
---
RS-485
---
RS-232C
RS-485
Previous model
Thermocou-
ple input
Resistance
thermome-
ter input
E5GN-RTC E5GN-RP
E5GN-R1TC E5GN-R1P
--- ---
--- ---
E5GN
E5GN
-R03TC-FLK -R03P-FLK
--- ---
--- ---
--- ---
--- ---
E5GN-QTC E5GN-QP
E5GN-Q1TC E5GN-Q1P
--- ---
--- ---
E5GN
E5GN
-Q03TC-FLK -Q03P-FLK
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
--- ---
New model
E5GN-RT-C
E5GN-R1T-C
E5GN-R1BT-C
E5GN
-R101T-C-FLK
E5GN
-R103T-C-FLK
E5GN-R2T-C
E5GN-R2HT-C
E5GN-R2BT-C
E5GN
-R203T-C-FLK
E5GN-QT-C
E5GN-Q1T-C
E5GN-Q1BT-C
E5GN
-Q101T-C-FLK
E5GN
-Q103T-C-FLK
E5GN-Q2T-C
E5GN-Q2HT-C
E5GN-Q2BT-C
E5GN
-Q203T-C-FLK
E5GN-C1T-C
E5GN-C1BT-C
E5GN
-C101T-C-FLK
E5GN
-C103T-C-FLK
*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that
can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.
*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible
for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease
by one.
6

6 Page









E5GN pdf, datenblatt
E5GN
www.DataSheet4U.com
Characteristics
Indication accuracy
Influence of temperature *2
Influence of voltage *2
Input sampling period
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Affect of signal source
resistance
Insulation resistance
Dielectric strength
Vibration
resistance
Malfunction
Destruction
Shock
resistance
Malfunction
Destruction
Weight
Degree of protection
Memory protection
Setup Tool
Setup Tool port
Standards
Approved
standards
Conformed
standards
EMC
Thermocouple: *1
(±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer input:
(±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit max.
Analog input:
±0.2% FS ±1 digit max.
CT input:
±5% FS ±1 digit max.
Thermocouple input (R, S, B, W, PL II):
(±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: *3
(±1% of PV or ±4°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer input:
(±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input:
(±1%FS) ±1 digit max.
250 ms
Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4
Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS)
Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4
Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
0 to 3999 s (in units of 1 s)
0 to 3999 s (in units of 1 s) *5
0.5, 1 to 99 s (in units of 1 s)
0.0 to 100.0% (in units of 0.1%)
1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/max. (100 max.)
Platinum resistance thermometer: 0.1°C/max. (10 max.)
20 Mmin. (at 500 VDC)
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
100 m/s2, 3 times each in X, Y, and Z directions
300 m/s2, 3 times each in X, Y, and Z directions
Controller: Approx. 90 g, Mounting Bracket: Approx. 10 g
Front panel: IP66, Rear case: IP20, Terminals: IP00
Non-volatile memory (number of writes: 1,000,000 times)
CX-Thermo version 4.2 or higher
Provided on the side of the E5GN. Connect this port to the computer when using the Setup Tool. An E58-CIFQ1 USB-Serial
Conversion Cable is required to connect the computer to the port on the side of the E5GN. *6
UL 61010-1, CSA C22.2 No. 1010-1
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI:
EN 61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EN 55011 Group 1, class A
EMS:
EN 61326
ESD Immunity:
EN 61000-4-2
Electromagnetic Field Immunity:
EN 61000-4-3
Burst Noise Immunity:
EN 61000-4-4
Conducted Disturbance Immunity:
EN 61000-4-6
Surge Immunity:
EN 61000-4-5
Power Frequency Magnetic Field Immunity:
EN 61000-4-8
Voltage Dip/Interrupting Immunity:
EN 61000-4-11
*1. The indication accuracy of K thermocouples in the 200 to 1300°C range, T and N thermocouples at a temperature of 100°C max., and U
and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C,
whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ± 1 digit max.
*2. Ambient temperature: 10°C to 23°C to 55°C, Voltage range: 15% to 10% of rated voltage
*3. K thermocouple at 100°C max.: ±10° max.
*4. “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F.
*5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s).
*6. External serial communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time.
12

12 Page





SeitenGesamt 17 Seiten
PDF Download[ E5GN Schematic.PDF ]

Link teilen




Besondere Datenblatt

TeilenummerBeschreibungHersteller
E5GNBasic-type Digital Temperature ControllerOmron
Omron

TeilenummerBeschreibungHersteller
CD40175BC

Hex D-Type Flip-Flop / Quad D-Type Flip-Flop.

Fairchild Semiconductor
Fairchild Semiconductor
KTD1146

EPITAXIAL PLANAR NPN TRANSISTOR.

KEC
KEC


www.Datenblatt-PDF.com       |      2020       |      Kontakt     |      Suche