Número de pieza E5ER-T
Descripción Programmable Temperature Controller
Fabricantes Omron 
Logotipo Omron Logotipo



Hay una vista previa y un enlace de descarga de E5ER-T (archivo pdf) en la parte inferior de esta página.


Total 10 Páginas

No Preview Available ! E5ER-T Hoja de datos, Descripción, Manual

Programmable Digital Controller
E5ER-T
A new 48 × 96-mm High-speed, High-
precision Digital Controller that is
Programmable!
• Create up to 32 programs with up to 256 segments total.
• 0.01°C High resolution for Pt input.
• High-speed sampling at 50 ms.
• Settings easily made from a computer using the CX-Thermo.
• RoHS compliance for world-wide application.
Refer to Safety Precautions for All E5@R
Models.
Model Number Structure
www.DataSheet4U.com
CSM_E5ER-T_DS_E_3_1
Model Number Legend
E5ER-T@@@@@@@@-@@@
1 2 3 4 56 7 8 9
1. Control method
Blank:Standard or heating/cooling control
P: Position proportional control
2. Output 1
R: NO relay output + NO relay output
Q: Pulse output/current output + pulse output
C: Current output + current output
3. Output 2
R: NO relay output + NO relay output
Q: Pulse output/current output + pulse output
C: Current output + current output
4. Auxiliary Outputs
Blank:None
4: NO relay output + NO relay output
T: 2 transistor outputs
5. Communications
Blank: None
3: RS-485 communications
6. Optional Function
Blank: None
D: 4 event inputs
7. Input 1
B: Universal-input and 2 event inputs
F: Universal-input and FB
W: Universal-input and universal-input
8. Input 2
Blank: None
W: Universal-input and universal-input
9. Other
FLK: CompoWay/F communications
(3 digits): (Modification type)
Note: The above model number legend is intended as a functional description of models. Not all possible combinations of functions are available.
Confirm model availability in Ordering Information when ordering.
Note: Be sure to read the precautions for correct use and other precautions in the following user's manual before using the Digital
Controller.
E5AR/ER Digital Controller User's Manual (Cat. No. Z182)
1

1 page




E5ER-T pdf
Communications Specifications
Transmission path connection
Multiple points
Communications method
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
Baud rate
9,600, 19,200, or 38,400 bps
Transmission code
ASCII
Data bit length
7 or 8 bits
Stop bit length
1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Block check character (BCC): CompoWay/F
CRC-16: Modbus
Flow control
None
Interface
RS-485
Retry function
None
Communications buffer
217 bytes
Communications response send wait time 0 to 99 ms, Default: 20 ms
E5ER-T
www.DataSheet4U.com
Program Control Functions
Number of programs (patterns)
Number of segments (steps)
Maximum number of segments
Segment setting method
Segment times
Alarm group num- Number of sets
ber specifications Setting method
Reset operation
Startup operation
PID sets
Number of sets
Setting method
Alarm SP function
Program status Segment operation
control
Program operation
Wait operation Wait method
Wait width setting
Setting method
Time signals
Number of outputs
Number of ON/OFF
operations
Setting method
Segment outputs Number of outputs
Setting method
Program status output
Program startup PV start
operation
Standby
Operation end operation
Number of event inputs
32 (with 8 segments/program)
32 (with 8 programs)
256
Time setting (Segment set with set point and time.)
Gradient setting (Segment set with set point, gradient, and time.)
0 h 0 min to 99 h 59 min
0 min 0 s to 99 min 59 s
0 min 00.0 s to 99 min 59.9 s
4
Set separately for each program.
Select either stopping control or fixed SP operation.
Select continuing, resetting, manual operation, run mode, or ramp back operation.
8
Set separately for each program (automatic PID group selection also supported).
Select from ramp SP and target SP.
Advance, hold, and back
Program repetitions and program links
Select from waiting at segment ends and always waiting.
Wait width upper limit and lower limit set separately for each program.
ON/OFF setting for each segment
6
3 each per output
Set separately for each program.
10
ON/OFF set for each segment.
Program end output (pulse width can be set)
Segment number output
Select from segment 1 set point, gradient-priority PV start, and time-priority PV start.
Standby
Select from resetting, continuing control at final set point, and fixed SP control.
10 max.
5

5 Page










PáginasTotal 10 Páginas
PDF Descargar[ Datasheet E5ER-T.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
E5ER-TProgrammable Temperature ControllerOmron
Omron

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar