Datenblatt-pdf.com


DHR-C5 Schematic ( PDF Datasheet ) - LEM

Teilenummer DHR-C5
Beschreibung AC/DC Current transducer
Hersteller LEM
Logo LEM Logo 




Gesamt 3 Seiten
DHR-C5 Datasheet, Funktion
AC/DC Current transducer DHR-C5
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement). True RMS 0-5V
voltage output.
IPN = 100..1000 A
Electrical data
Primary Nominal
DC & AC Current
IPN (A.t.RMS)
100
200
300
400
500
600
1000
Primary AC Current
Max. Peak Value (*)
IP (A)
600
600
1000
1000
1800
1800
1800
Output voltage
(Analog)
VOUT (VDC)
0-5
0-5
0-5
0-5
0-5
0-5
0-5
R Load resistance
L
VC Supply voltage
IC Current consumption
VSL Output voltage limitation (0-5V)
ÎP Overload capability (Ampere Turns)
Performance data
X
εL
VOE
TCVOE
TCVOUT
tr
BW
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (1% of I .. ± I )
PN PN
Electrical offset voltage, TA = 25°C
Temperature coefficient of VOE ( 0..+60 °C)
(-40..+70 °C)
Temperature coefficient of VOUT (% of reading)
Response time to 90 % of IPN step
Frequency bandwidth (±1dB)
General data
TA
TS
m
IPxx
Ambient operating temperature
Ambient storage temperature
Mass
Protection degree
Type
DHR 100 C5
DHR 200 C5
DHR 300 C5
DHR 400 C5
DHR 500 C5
DHR 600 C5
DHR 1000 C5
10
k
+ 20 .. 50 V DC
30 mA
<7 V
30000
A.t
< ± 1 % of IPN
< ± 1.0 % of I
PN
< ± 1.0 % of IPN
± 2.0 mV/K
± 4.0 mV/K
± 0.1
%/K
< 150
ms
DC 20..6000Hz
- 40 .. + 70
- 40 .. + 85
260
IP20
°C
°C
g
Note :
(*) The Max. Peak AC Current is the highest peak level of the primary signal that is
taken into account for accurate True RMS calculation. Yet the device is designed for
maximum continuous True RMS value equal to IPN, whereas the output is limited by
the above specified output limitation.
Features
VFD and SCR waveforms current
measurement
True RMS output
Panel mounting
Eliminates insertion loss
Insulated plastic case recognized
according to UL94-V0
Advantages
Large aperture for cable up to
Ø32mm
High isolation between primary and
secondary circuits
Easy installation
Applications
VFD Controlled Loads
VFD output indicates how the motor
and attached load are operating.
SCR Controlled Loads
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
Switching Power Supplies and
Electronic Ballasts
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Application domain
Energy and Automation
061128/14
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com





SeitenGesamt 3 Seiten
PDF Download[ DHR-C5 Schematic.PDF ]

Link teilen




Besondere Datenblatt

TeilenummerBeschreibungHersteller
DHR-C10AC/DC Current transducerLEM
LEM
DHR-C420AC/DC Current transducerLEM
LEM
DHR-C5AC/DC Current transducerLEM
LEM

TeilenummerBeschreibungHersteller
CD40175BC

Hex D-Type Flip-Flop / Quad D-Type Flip-Flop.

Fairchild Semiconductor
Fairchild Semiconductor
KTD1146

EPITAXIAL PLANAR NPN TRANSISTOR.

KEC
KEC


www.Datenblatt-PDF.com       |      2020       |      Kontakt     |      Suche