Número de pieza | DPT103D-1003D | |
Descripción | (DPTxxx) 3-Wire Differential Pressure Transmitters Current Output | |
Fabricantes | Honewell | |
Logotipo | ||
Hay una vista previa y un enlace de descarga de DPT103D-1003D (archivo pdf) en la parte inferior de esta página. Total 2 Páginas | ||
No Preview Available ! DPT53-1003 / DPT103D-1003D
3-WIRE DIFFERENTIAL PRESSURE TRANSMITTERS
CURRENT OUTPUT
DPT53-1003
GENERAL
The differential pressure transmitters of the DPT series are
used for measuring differential pressure, positive pressure,
and vacuum. The transmitters are suitable for:
• air-conditioning,
• building automation,
• environmental protection,
• valve and flap control,
• filter and blower monitoring,
• fluid and level monitoring, and
• control of air flows.
NOTE:
Because these sensors do not fulfill FDA require-
ments, it is not permitted to employ them in critical
pharmaceutical applications under continuous FDA
supervision.
Models
order no.
pressure range
12
DPT53
-50...0...+50 Pa1)
n.a.
DPT113
-100...0...+100 Pa1)
n.a.
DPT103/103D
0...100 Pa1)
0...250 Pa
DPT253/253D
0...250 Pa1)
0...500 Pa
DPT503/503D
0...500 Pa1)
0...1 kPa
DPT1003/1003D
0...1 kPa2)
0...2.5 kPa
1) ≤ ± 5% of FS; 2) ≤ ± 2.5% of FS
overload
capacity
20 kPa
20 kPa
20 kPa
20 kPa
20 kPa
40 kPa
bursting
pressure
40 kPa
40 kPa
40 kPa
40 kPa
40 kPa
70 kPa
® U.S. Registered Trademark
Copyright © 2004 Honeywell Inc. • All rights reserved
www.DataSheet4U.com
SPECIFICATION DATA & MOUNTING INSTRUCTIONS
FEATURES
• Monitoring gaseous, non-aggressive media
• Piezo-resistive pressure transducer
• Up to 40 kPa overload capacity
• Models with display (DPT103D-1003D)
• Rugged design; protection class IP54
• Easy installation and wiring connection
• Measurement range adjustable by jumper
• Response time adjustable by jumper
SPECIFICATION
Supply voltage
Output signal
Maximum load
Pressure medium
Working temperature
Linearity and hysteresis error
Temperature error at 0...50°C
Storage temperature
Humidity
Long-term stability, typical
DPT53...503
DPT1003
Repetition accuracy
Position dependence
Response time
Process connection
Electrical connection
Housing material
Cable entry
Protection class
EMV
Weight
18...24...30 Vac; 50/60 Hz or
16...24...32 Vdc
4...20 mA, three-wire
≤ 500 Ω *
Air and non-aggressive
gases
0...50 °C
≤ ± 1.0% of FS
≤ ± 1.0% of FS
1) ≤ ± 5.0% of FS
2) ≤ ± 2.5% of FS
-10...+70 °C
0...95% rh, non-condensing
≤ ± 2.5% of FS per year
≤ ± 1.5% of FS per year
≤ ± 0.2% of FS
≤ ± 0.02% of FS per g
1 s (switchable to 100 ms)
6 mm hose pipe
Screw terminal block for wire
up to 1.5 mm²
ABS and POM
M20x1.5 (polyamide)
IP54 as per EN60529
EN60770, EN61326
approx. 130 g
*Device is calibrated under a resistive load of 100 Ω.
Maximum load of 500 Ω requires AC/DC power supply ≥ 24 V
www.DataSheet4U.com
EN0B-0465GE51 R0804
1 page |
Páginas | Total 2 Páginas | |
PDF Descargar | [ Datasheet DPT103D-1003D.PDF ] |
Número de pieza | Descripción | Fabricantes |
DPT103D-1003D | (DPTxxx) 3-Wire Differential Pressure Transmitters Current Output | Honewell |
Número de pieza | Descripción | Fabricantes |
SLA6805M | High Voltage 3 phase Motor Driver IC. |
Sanken |
SDC1742 | 12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters. |
Analog Devices |
DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares, |
DataSheet.es | 2020 | Privacy Policy | Contacto | Buscar |