DataSheet.es    


PDF CKB-38-xxxx Data sheet ( Hoja de datos )

Número de pieza CKB-38-xxxx
Descripción Mid-Priced CMOS IC Time Delay Relay
Fabricantes Tyco 
Logotipo Tyco Logotipo



Hay una vista previa y un enlace de descarga de CKB-38-xxxx (archivo pdf) en la parte inferior de esta página.


Total 2 Páginas

No Preview Available ! CKB-38-xxxx Hoja de datos, Descripción, Manual

Catalog 1308242
Issued 3-03
CK series
P&B
Mid-Priced CMOS IC Time Delay Relay
Choice of timing modes
– Delay on operate
– Delay on release
– Delay on dropout (no input required during timing)
– Interval on
Knob or resistor adjustable types
10A output relay with DPDT contacts
Various models time from 0.1 to 180 sec.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Timing Modes
Delay on operate – Delay period begins when input voltage is applied. At
the end of the delay period, the relay will operate and will not release until
input voltage is removed. Reset occurs when input voltage is reapplied.
INPUT
VOLTAGE
N.O. RELAY
CONTACTS
ON
OFF
ON
OFF
TIME
Contact Data @ 25°C
Arrangements: 2 Form C (DPDT).
Material: Silver-cadmium oxide alloy.
Rating: 10A @ 30VDC or 277VAC, resistive; 1/2 HP @ 250VAC; 1/3 HP @
120VAC.
Expected Mechanical Life: 10 million operations.
Expected Electrical Life: 100,000 operations, min., at rated load.
Delay on release – Input voltage must be applied continuously to operate
the internal relay. When the control switch is closed, the relay energizes.
When the control switch is opened, timing begins. When timing is
complete, the relay will de-energize. Time may be reset to zero during
timing by closing the control switch.
CONTROL
SWITCH
ON
OFF
N.O. RELAY ON
CONTACTS OFF
TIME
Delay on dropout – The relay operates immediately upon application of
input voltage. Timing begins when input voltage is removed. When timing
is complete, the relay will de-energize. Reset occurs when input voltage is
reapplied.
INPUT
VOLTAGE
N.O. RELAY
CONTACTS
ON
OFF
ON
OFF
TIME
Interval on (with control switch) – Input voltage must be applied
continuously to operate the internal relay. The relay energizes and timing
begins when the external switch is closed. At the end of the time delay
period the relay will de-energize. Reset is accomplished by opening and
reclosing the control switch.
CONTROL
SWITCH
N.O. RELAY
CONTACTS
ON
OFF
ON
OFF
TIME
Timing Specifications
Timing Ranges: From 0.1 to 180 sec.
Timing Adjustment: External resistor and knob adjustable.
Tolerance (for AC units add ±1/2 cycle 60 Hz.):
Knob Adj. Types:–0, +20% of max. specified at high end of timing range;
min. specified, or less, at low end.
Fixed Types: ± 5%.
Res. Adj. Types: ± 5% at high end of timing range; min. specified, or less,
at low end.
Delta Time (for AC units add ±1 cycle 60 Hz.): ± 10%.
Repeatability (for AC units add ±1 cycle 60 Hz.): ± 2%.
Release Time: 60 ms, typ.; 100 ms, max.
Recycle Time: 60 ms, typ.; 100 ms, max.
Dimensions are shown for
1224 reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Initial Dielectric Strength
Between Open Contacts: 500V rms, 60 Hz.
Between All Other Conductors: 500V rms, 60 Hz.
Input Data @ 25°C
Voltage: 24 & 120VAC and 12 & 24VDC.
Power Requirement: AC Types: Typically less than 3 VA.
DC Types: Typically less than 3 W.
Initiate Time: Delay on dropout timers must have input voltage applied for
a minimum of three seconds for dropout function to be
guaranteed.
Transient Protection: Yes.
Reverse Voltage Protection: Yes.
Input Voltages & Limits @ 25°C
Voltage
Type
Nominal
Voltage
Minimum
Voltage
Maximum
Voltage
AC 24
120
DC 12
24
20
105
11
20
Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).
AC models will operate on 50 or 60 Hz.
28
130
13
32
Environmental Data
Temperature Range: Storage: -55°C to +85°C.
Operating: -10°C to +55°C.
Mechanical Data
Termination: 8- or 11-pin octal style plug.
Enclosure: White plastic case. Knob adjustable types have dial scale for
reference only.
Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on)
screw terminal sockets. 11-pin types fit either 27E123 or
27E892 (snap-on) screw terminal sockets.
Weight: 6 oz. (170g) approximately.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.

1 page





PáginasTotal 2 Páginas
PDF Descargar[ Datasheet CKB-38-xxxx.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
CKB-38-xxxxMid-Priced CMOS IC Time Delay RelayTyco
Tyco

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar